BUILDING AUTOMATION
Output 1~4
Switch/Curtain
AC/Heating/Cooling/2-pipe
Curtain DC Fan control Valve control (4-pipe)
Switch Curtain AC Heating/Cooling /2-pipe
Output 1 Output 1
Curtain 1
Valve 1 (Output 1&2, if 3 point,
open and close)
Curtain DC 1
Fan 1: fan speed 1
Valve 1: Heat
(Output 1&2, if 3 point, open and close)
Output 2 Output 2 Fan 1: fan speed 2
Output 3 Output 3
Curtain 2
Valve 2 (Output 1&2, if 3 point,
open and close)
Fan 1: fan speed 3
Valve 1: Cool
(Output 3&4, if 3 point, open and close)
Output 4 Output 4
From the above table, it can be seen that one switch Output occupies one Output channel, one curtain Output (AC) occupies two Output channels, one curtain Output
(DC) occupies four Output channels, and the fan Output determines the Output according to the level of fan speed. The valve output determines the number of switch
output channels occupied according to the HVAC control mode and valve type, such as Heating/Cooling/2-pipe occupy one or two switch output channels, while 4-pipe
occupy two or four switch output channels.
Under Fan control functions, if some Output is not used, these Outputs can be used to switch Output, depending on the Parameter setting.
Comment Parameter Description (similar function, one of which is taken as an example):
• Parameter “Curtain 1 output is fixed for”: Output 1(Up/Open) &Output 2(Down/Close)
This Parameter indicates that the Output Channel with AC Motor Curtain 1 is fixed to Output 1 and Output 2. Output 1 is connected to Up/Open, Output 2 is con-
nected to Down/Close.
• Parameter “External DC+ input”: Output 1&Output 3
• Parameter “External DC- input”: Output 2&Output 4
• Parameter “Output Driver”: C
The three parameters indicate the wiring mode of the DC motor curtain output. The positive input of the motor is connected to Output 1 and Output 3 (Output 1 and
3), and the negative input of the motor is connected to Output 2 and Output 4 (Output 2 and 4). The drive is connected to C.
• Parameter “Fan 1 output is fixed for”: 1level:1; 2level:1&2; 3level:1&2&3
This Parameter indicates that the fan with level 1 fan speed has an Output channel of Output 1;
For fans with 2 levels of fan speed, the Output channels are Output 1 and Output 2;
For fans with 3 fan speeds, the Output channels are Output 1, Output 2 and Output 3.
• Parameter “If Fan 1 set to 1 or 2 level, output 3&4 as switch output”:
Note: If the fan type is level 1 or level 2, Output3 and Output4 can be used as the switch Output.
The following two parameters for describing the output of 4-pipe valve:.
• Parameter “Heat output for 4-pipe valve 1 is Output 1”: Output 1&2, if 3 point, open and close
This Parameter indicates that the heating Output channel of valve 1 is Output 1;
That is, for a two-wire valve, one end of the valve is connected to Output 1, and the other end is connected to C that supplies power to the valve.
If it is a three-wire valve type, the Output channels are Output 1 and Output 2;
That is, for a three-wire valve, both ends of the valve are connected to Output 1 and Output 2, and the other end is connected to C that supplies power to the valve.
• Parameter “Cool output for 4-pipe valve 1 is Output 3”: Output 3&4, if 3 point, open and close
This Parameter indicates that the cooling output channel of valve 1 is Output 3;
That is, for a two-wire valve, one end of the valve is connected to Output 3 and the other end is connected to C that supplies power to the valve.
If it is a three-wire valve type, the Output channels are Output 3 and Output 4;
That is, a three-wire valve, the two ends of the valve are connected to Output 3 and Output 4, and the other end is connected to C that supplies power to the valve.
• Parameter “Valve 1 output is fixed for Output 1”: Output 1&2, if 3 point, open and close
This parameter is visible when HVAC control is selected as Heating/Cooling/2-pipe, for noting the output channel which corresponds to the valve.
If it is a two-wire valve, the output channel is Output 1, that is, one end of the valve is connected to Output 1, and the other end is connected to C that supplies power
to the valve.
If it is a three-wire valve type, the Output channels are Output 1 and Output 2,that is,the two ends of the valve are connected to Output 1 and Output 2; the other end
of the valve is connected to
Un that supplies power to the valve.
Parameter setting description in the ETS