the commissioning. Another leak test should be performed when leaving
the area.
ā–ˆ Scrapping and recycling
ā— announce invalidated check in paper
Before this procedure, the technician should be fully familiar with the
equipment and all its characteristics. The practice of safe refrigerant
recovery is recommended. If the recovered refrigerant is reused, samples
of refrigerant and oil shall be analyzed before operation. The required
power supply shall be guaranteed prior to testing.
1. Familiar with the equipment and operation;
2. Disconnect the power supply;
3. Ensure that before proceeding with this procedure;
A, If necessary, the mechanical operation equipment shall facilitate the
operation of the refrigerant storage tank;
B. All habeas protection devices are effective and can be used correctly;
C. The whole recycling process should be carried out under the
guidance of qualified personnel;
D. Recycling equipment and storage tanks shall meet the
corresponding standards.
4. If possible, the refrigeration system should be evacuated;
5. If the vacuum state cannot be reached, it should be extracted from
multiple places to extract the refrigerant in each part of the system;
6. Ensure that the capacity of the storage tank is sufficient before starting
the recycling;
7. Start up and operate the recovery equipment according to the
manufacturer's operation instructions;
8. Don't overfill the tank.(The liquid injection volume shall not exceed 80%
of the storage tank volume);
9. Even if it lasts for a short time, it shall not exceed the maximum
working pressure of the storage tank;
10. After the tank filling and the operation process is complete, ensure
that the tank and equipment are removed quickly and all the stop valves
on the equipment are closed;
11. The recycled refrigerant shall not be injected into another refrigeration
system before purification and inspection.
Pay attention to:
The air conditioner shall be marked after scrapping and emptying the
refrigerant, with the date and endorsement. Ensure that the identification
on the air conditioner reflects the R290 refrigerant contained by the air
conditioner.