- 22 -
34
Battery equalization
voltage
48V models default setting is 58.4V. Setting range is from
floating voltage ~ 64V. Increment of each click is 0.1V.
24V models default setting is 29.2V. Setting range is from
floating voltage ~ 31V. Increment of each click is 0.1V.
35
Battery equalized
time
60min (default)
Setting range is from 0 min to
900min.
36
Battery equalized
timeout
120min (default)
Setting range is from 0min to
900 min.
37
Equalization interval
30days (default)
Setting range is from 1 to 90
days.
39
Equalization
activated
immediately
Enable
Disable (default)
If equalization function is enabled in program 33, this program
can be set up. If Enable is selected in this program, it’s to
activate battery equalization immediately and LCD main page
will shows ”. If “Disable” is selected, it will cancel
equalization function until next activated equalization time
arrives based on program 37 setting. At this time, “Eq” will
not be shown in LCD main page..