4.8 Baying the Racks
Two or more racks of the same height can be bayed with the supplied baying brackets. The brackets have three hole
locations (shown in Figure 4.12 on the facing page :
The single hole connects to the rack
The outer holes bay the racks on 24in.(609.6mm) centers for floor-tile placement. When bayed on 24-in.
centers, there is a gap between the frames that must be sealed with a baying-gasket kit, part VRA5003, to
maintain proper airflow.
The center holes put the racks on metric centers.
Connecting the racks is easier if they are in their final installation position before baying.
WARNING! The rack-baying brackets and hardware are not a ground-bond method. For more details on
properly grounding, see Grounding the Rack on the facing page .
NOTE: The kit is for 24-in. wide spacing only.
When baying racks together on 24-in. centers, use a Baying Gasket Kit (part VRA5003) to seal the gap between the racks to
maintain proper hot-aisle/cold-aisle best practices. The gasket must be installed before baying racks.
To install the gasket:
1. Measure and cut gasket to length.
2. peel adhesive backing from the gasket, and place the gasket around side perimeter of one of the racks.
3. Position the racks next to each other with the gasket between them.
The racks are ready for baying.
Figure 4.11 Baying gasket location
4 Installation and Assembly Procedures
20
Vertiv™ VR Installer/User Guide

Bekijk gratis de handleiding van Vertiv VR3100TAA, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkVertiv
ModelVR3100TAA
CategorieNiet gecategoriseerd
TaalNederlands
Grootte4208 MB

Caratteristiche Prodotto

Kleur van het productBlack, Transparent
Gewicht127000 g
Breedte600 mm
Diepte1100 mm
Hoogte2000 mm