3.3 Equipment Clearance Requirements
When planning the position and location of the rack, refer to Figure 3.3 below , for the required clearances for installation and
service of the rack and installed equipment.
Figure 3.3 Required clearance
 Item
600-mm (23.62in.) wide, mm (in.) 800-mm (31.5 in.) wide, mm (in.)
x 1100mm (43.31 in.) x 1200m(47.24 in.) x 1100mm (43.31 in.) x 1200mm (47.24 in.)
1 1992 (78.43) 2092 (82.36) 2280 (89.76) 2393 (94.21)
2 319 (12.54) 421 (16.57)
3 1066 (41.97) 1434 (56.46)
4 1087 (42.79) 1456 (57.32)
5 610 (24.02) 809 (31.85)
6 148° maximum door swing, 3 places
Table 3.1 Clearance Distances