of its mechanical installation and electrical connections should be carried out. At least two staff
members should conduct the inspection according to the items listed in the table below. Records
should be kept during the inspection. If any items that do not meet national, industry, and regulatory
requirements are found, they should be corrected immediately.
Mechanical installation inspection
The energy storage system is not deformed or damaged
The bottom of the energy storage system is fixed and the support is stable and reliable
There is plenty of space around the energy storage system
The temperature, humidity and ventilation conditions of the environment where the energy storage
system is located meet the requirements
The cooling air circulates smoothly
The cabinet body has complete and reliable sealing protection
Electrical installation inspection
The grounding of the energy storage system is complete and firm
The positive and negative poles of the DC input are connected correctly, and the tightening torque
meets the requirements
The communication wiring is correct and should be kept at a certain distance from other cables
The cable wire numbers are marked correctly, clearly and easily distinguishable
The insulating protective cover is complete and reliable, and the danger warning label is clear and
firm
Other examinations
All the vacant cables are fastened tightly with insulating cable ties
There are no remaining tools, parts, conductive dust or other foreign objects from drilling inside the
cabinet
There is no condensed moisture or ice inside the cabinet