09 Safety
User Manual
Incorrect grounding can cause physical injury, death or equipment
malfunction and electromagnetic radiation increase.
Make sure that grounding conductor is adequately sized as
required by safety regulations.
Do not connect the ground terminals of the unit in series in case of
a multiple installation. This product can cause current with a DC
component, where a residual current device (RCD) or monitoring
(RCM) is used for protection.
In case of direct or indirect contact, only an RCD or RCM of type B
is allowed on the supply side of this product.
The installation that connects the equipment to the supply
terminals shall comply with the requirements of BS 7671.
No protection settings can be altered.
User shall ensure that equipment is so installed, designed and
operated to maintain at all times compliance with the requirements
of ESQCR22(1)(a).
Electrical installation and maintenance shall be conducted by
licensed electrician and shall comply with Australia National Wiring
Rules.
HiEnergy Series inverter can be operated with high voltage battery
voltage and nominal capacity etc., please refer to the parameters
list.
To prevent potential electric shock and short-circuit current
hazards that may arise from accumulator batteries, it is advised to
follow the following precautions while the battery replacement: