Tru Components DPH-12054 handleiding
Handleiding
Je bekijkt pagina 13 van 20

BN 3427719 3427721 3427722 3428342
Customer # TC-YSD60S-0504500 TC-YSD100S-1207100 TC-YSD100S-2403830 TC-YSD30S-0503000
Product name
Din Rail Power Supply 5V/DC 4.5A
22.5W
Din Rail Power Supply 12V/DC 7.1A
85.2W
Din Rail Power Supply 24V/DC 3.83A
92W
Din Rail Power Supply 5V/DC 3A 15W
Rated input 100-240 V/AC, 50/60 Hz 100-240 V/AC, 50/60 Hz 100-240 V/AC, 50/60 Hz 100-240 V/AC, 50/60 Hz
Input voltage range 90-264 V/AC or 127-370 V/DC 90-264 V/AC or 127-370 V/DC 90-264 V/AC or 127-370 V/DC 90-264 V/AC or 127-370 V/DC
Frequency range 47-63 Hz 47-63 Hz 47-63 Hz 47-63 Hz
Efciency (Typ.) 85% 88% 90% 82%
AC current (Typ.)
1.2 A/115 V/AC
0.8 A/230 V/AC
3A/115 V/AC
1.6 A/230 V/AC
3A/115 V/AC
1.6 A/230 V/AC
0.88 A/115 V/AC
0.48 A/230 V/AC
Inrush current (Typ.)
30 A/115 V/AC
60 A/230 V/AC
35 A/115 V/AC
70 A/230V/AC
35 A/115 V/AC
70 A/230 V/AC
25 A/115 V/AC
45 A/230 V/AC
Leakage current 0.707 mA/264 V/AC 0.707 mA/264 V/AC 0.707 mA/264 V/AC 0.707 mA/264 V/AC
Power Factor Correction (PFC) NA NA NA NA
Ripple & Noise (max.) 80 mVp-p 120 mVp-p 150 mVp-p 80 mVp-p
Voltage tolerance ±2.0 % ±2.0 % ±2.0 % ±2.0 %
Line regulation ±1.0 % ±1.0 % ±1.0 % ±1.0 %
Load regulation ±1.0 % ±1.0 % ±1.0 % ±1.0 %
Setup, rise time
500 ms, 50 ms/230 V/AC at full load
500 ms, 50 ms/115 V/AC at full load
500 ms, 50 ms/230 V/AC at full load
500 ms, 50 ms/115 V/AC at full load
500 ms, 50 ms/230 V/AC at full load
500 ms, 50 ms/115 V/AC at full load
500 ms,50 ms/230 V/AC at full load
500 ms, 50 ms/115 V/AC at full load
Hold up time (Typ.)
30 ms/230 V/AC at full load
12 ms/115 V/AC at full load
30 ms/230 V/AC at full load
12 ms/115 V/AC at full load
30 ms/230 V/AC at full load
12 ms/115 V/AC at full load
30 ms/230 V/AC at full load
12 ms/115 V/AC at full load
Voltage adjustment range 5.0 - 5.5 V/DC 12-13V/DC 24-25.5 V/DC 4.5 - 5.5 V/DC
Output voltage (min.) 5 V/DC 12 V/DC 24 V/DC 5 V/DC
Output voltage (max) 5.5 V/DC 13 V/DC 25.5 V/DC 5.5 V/DC
Output current (max) 4.5 A 7.1 A 3.83 A 3 A
Rated Power 22.5 W 85.2 W 92 W 15 W
Output power characteristic N/A N/A N/A N/A
DC power good signal N/A N/A N/A N/A
Withstand voltage
I/P-O/P: 3 kV/AC
I/P-FG: 2 kV/AC
O/P- FG: 0.5 kV/AC
I/P-O/P: 3 kV/AC
I/P-FG: 2 kV/AC
O/P- FG: 0.5 kV/AC
I/P-O/P: 3 kV/AC
I/P-FG: 2 kV/AC
O/P- FG: 0.5 kV/AC
I/P-O/P: 3 kV/AC
I/P-FG: 2 kV/AC
O/P- FG: 0.5 kV/AC
Isolation resistance
I/P-O/P: > 100M Ohms / 500V/DC /
25 °C / 70% RH
I/P-O/P: > 100M Ohms / 500V/DC /
25 °C / 70% RH
I/P-O/P: > 100M Ohms / 500V/DC /
25 °C / 70% RH
I/P-O/P: > 100M Ohms / 500V/DC /
25 °C / 70% RH
DIN rail compatability
TS-35/7.5 or TS-35/15
EN/IEC 60715 (DIN rail)
TS-35/7.5 or TS-35/15
EN/IEC 60715 (DIN rail)
TS-35/7.5 or TS-35/15
EN/IEC 60715 (DIN rail)
TS-35/7.5 or TS-35/15
EN/IEC 60715 (DIN rail)
Output connection type Screw DIN terminal Screw DIN terminal Screw DIN terminal Screw DIN terminal
Input / output connector pin
count
Input: 2 poles
Ouput: 4 poles
Input: 2 poles
Ouput: 4 poles
Input: 2 poles
Ouput: 4 poles
Input: 2 poles
Ouput: 2 poles
Outputs 1 1 1 1
Operating orientation Vertical (input terminals down) Vertical (input terminals down) Vertical (input terminals down) Vertical (input terminals down)
Protection mechanisms Short circuit, overload, over voltage
Short circuit, over load, over voltage,
over temperature
Short circuit, over load, over voltage,
over temperature
Short circuit, overload, over voltage
Overload protection behaviour
Trip Point: hiccup mode
Recovery: Automatic after fault
condition is removed
Trip Point: hiccup mode
Recovery: Automatic after fault
condition is removed
Trip Point: hiccup mode
Recovery: Automatic after fault
condition is removed
Trip Point: hiccup mode
Recovery: Automatic after fault
condition is removed
Overvoltage protection
Trip point: 5.75-6.75 V
Action: Output shutdown
Recovery: After discharge, restart the
power supply to recover
Trip point: 14.2-16.2 V
Action: Output shutdown
Recovery: After discharge, restart the
power supply to recover
Trip point: 30-36 V
Action: Output shutdown
Recovery: After discharge, restart the
power supply to recover
Trip point: 5.75-7.5 V
Action: Output shutdown
Recovery: After discharge, restart the
power supply to recover
Over temperature protection N/A N/A N/A N/A
Over voltage category II II II II
Cooling method Convection Convection Convection Convection
Fuse T3.15A/L250V T3.15A/L250V T3.15A/L250V T3.15A/L250V
Max. connected products per
circuit breaker
Type C16: 66 pcs
Type D16: 132 pcs
Type C16: 16 pcs
Type D16: 32 pcs
Type C16: 16 pcs
Type D16: 32 pcs
Type C16: 98 pcs
Type D16: 196 pcs
Terminal screw torque
Inputs: 0.4 N·m
Outputs: 0.5 N·m
Inputs: 0.4 N·m
Outputs: 0.5 N·m
Inputs: 0.4 N·m
Outputs: 0.5 N·m
Inputs: 0.4 N·m
Outputs: 0.4 N·m
Ingress protection IP20 IP20 IP20 IP20
Operating conditions -20 to +70 °C -20 to +70 °C -20 to +70 °C -20 to +70 °C
Operating humidity 20-90 % RH (non-condensing) 20-90 % RH (non-condensing) 20-90 % RH (non-condensing) 20-90 % RH (non-condensing)
Storage conditions -40 to +85 °C -40 to +85 °C -40 to +85 °C -40 to +85 °C
Storage humidity 10-95 % RH (non-condensing) 10-95 % RH (non-condensing) 10-95 % RH (non-condensing) 10-95 % RH (non-condensing)
Temperature derating De-rating from 45 - 70°C De-rating from 45 - 70°C De-rating from 45 - 70°C De-rating from 50 - 70 °C
Mean time between failures
(MTBF)
900K hrs min. MIL-HDBK-217F(25°C) 800K hrs min. MIL-HDBK-217F(25°C) 800K hrs min. MIL-HDBK-217F(25°C) 900K hrs min. MIL-HDBK-217F(25°C)
Weight 190 g 270 g 270 g 120 g
Bekijk gratis de handleiding van Tru Components DPH-12054, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Tru Components |
| Model | DPH-12054 |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 3027 MB |