VI. c - INITIATING A DEFROST (cont’d)
Manual or remote defrost start:
It’s possible to manually start a defrost, by pressing button
for 2 seconds.
Defrost type. Once defrost has started, Compressor and
Defrost outputs are controlled according to parameter
DTY. If FID = YES, the evaporator fans are active during
defrost.
Defrost termination. The actual defrost duration is
inuenced by a series of parameters.
• Time termination: T2 = NO and T3 different from 2EU:
the evaporator temperature is not monitored and defrost
will last as long as time DTO.
• Temperature monitoring of one evaporator: T2 = YES
and T3 different from 2EU. In this case, if the sensor
T2 measures the temperature DLI before the time DTO
elapses, defrost will be terminated in advance.
Resuming thermostatic cycle:
When defrost is over, if DRN is greater than 0, all outputs
will remain off for DRN minutes, in order for the ice to melt
completely and the resulting water to drain. Moreover, if
probe T2 is active (T2 = YES), the fans will re-start when
the evaporator gets to a temperature lower than FDD; Vice
versa, if probe T2 is not active (T2 = NO) or after defrost
has come to an end, such condition does not occur by end
of the time FTO, after FTO minutes have elapsed the fans
will be switched on anyway.
Caution: if DFM = NON or C-H = HEA all defrost functions
are inhibited; if DFT = 0, automatic defrost functions are
excluded.
VI. d - CONFIGURATION PARAMETERS
Parameter Conguration:
• To get access to the parameter conguration menu,
press button and for 5 seconds.
• With button or select the parameter to be
modied.
• Press button to display the value.
• By keeping button pressed, use button or to
set the desired value.
• When button is released, the newly programmed
value is stored and the following parameter is displayed.
• To exit from the setup, press button or wait for 30
seconds.
VI. e - TECHNICAL DATA
Power supply
TRL-002....W 100-240Vac ±10%, 50/60Hz, 3W
Relay output max loads (240Vac)
TRL-002..S/T..-. TRL-002..Q/R..-.
Compressor
16A resistive
12 FLA 48 RLA
12A resistive
12 FLA 48 RLA
Evap. Fan
16A resistive
4 FLA 12 RLA
8A resistive
4 FLA 12 RLA
Defrost
16A resistive
4 FLA 12 RLA
16A resistive
4 FLA 12 RLA
Auxiliary loads 1 7A resistive 7A resistive
Auxiliary loads 2 7A resistive 7A resistive
Input
NTC 10KΩ@25°C LAE Part No. SN4...
Measurement Range
<0.5 within the measurement range
Operating Conditions
-10... +50°C; 15%...80% r.H.
CE (Approvals and Reference Norms)
EN60730-1; EN60730-2-9; EN55022 (Class B); EN50082-1
VI. CONTROL BASICS (continued)