4.4. RM-320F Fireman's Microphone Extension
TheRM-320FisanexpansionunitfortheRM-300MFFiremansMicrophone.Upto3ExpansionUnitscanbe
added,expandingtheavailablefunctionkeystoupto20perunit.Zoneselection(1–20)andfailureindication/
acknowledgement functions can be assigned to each function key using the dedicated software.
1. Connection Cable
Used for connection to the RM-300MF or RM-
320F.
2. Indication Label Holder
Write the name, purpose, etc. of the indicator
and key on a label and insert the label into the
holder from the top. Labels can be printed using
the setting software. (For more information, refer
to "Printing Remote Microphone Labels" in the
separate software manual.)
3. Emergency Broadcast Zone/Failure Indicators
Indicator function assigned to each indicator is
determined by software settings.
Emergency Broadcast Zone Indicators (red)
Light to indicate emergency announcement
broadcastzones.
Failure Indicators (yellow)
Flash yellow (before failure acknowledgment) or
light yellow (after failure acknowledgment) when a
failure is detected.
Failure Reset Indicators* (yellow)
Remain lit while the Failure Reset key is pressed.
4. Broadcast Zone Indicators (green)
Lighttoindicatethecorrespondingselectedzone.
5.
Broadcast Zone Selector / Failure Acknowledgment
Keys / Failure Reset Key
Key function assigned to each keyis determined
by software settings.
Broadcast Zone Selector Keys
SelectbroadcastzoneswheninEmergencymode.
Failure Acknowledgment Keys
Keyscanbesettoacknowledgefailures.Whenan
assigned failure occurs, pressing the corresponding
key acknowledges the failure.
Failure Reset key*
Keycanbesettoresetfunctions.Whenafailure
occurs, remove the cause of the failure, then press
the corresponding key, reverting the unit back to
normal mode.
6. Expansion Connector
Connect the RM-320F Firemans Microphone
Extensiontothisconnector.
* This function can be used only when all the versions of VM-3000VA firmware, VM-3000E firmware, and
VM-3000 Setting Software are 2.00 or later.

Bekijk gratis de handleiding van Toa RM-300MF, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkToa
ModelRM-300MF
CategorieNiet gecategoriseerd
TaalNederlands
Grootte19502 MB

Caratteristiche Prodotto

Gewicht1100 g
Breedte200 mm
Diepte82.5 mm
Hoogte215 mm
Kleur behuizingWit