38. Power Supply Output Terminals
[VX-2000DS ONLY, PS OUT]
Supply power to the VX-2000DS Emergency
Power Supply. When the VX-2000DS is not
connected, use shorting bars to connect PS OUT
(+)toPOWERIN(+)andPSOUT(–)toPOWER
IN(–).
39. 24 V DC Input Terminals
[VX-2000DS ONLY, 24 V POWER IN]
Connect power from the VX-2000DS Emergency
PowerSupplyUnit.WhentheVX-2000DSisnot
connected, use shorting bars to connect PS OUT
(+)toDCPOWERIN(+)andPSOUT(–)toDC
POWERIN(–).
40. DIP switch (VM-3240VA and VM-3360VA only)
Used to perform equipment settings.
DIP Switch 1 [LINE/MIC]
Switches input sensitivity of Input 4. (ON: MIC,
OFF:LINE;Default:OFF)
DIP Switch 2 [NORMAL/EMERGENCY]
AlwayssetthisswitchtoOFF.(Default:OFF)
DIP Switches 3 – 5
Notused.(Default:OFF)
DIP Switches 6
Set to ON when excluding the front-mounted
emergency microphone from the surveillance
item.(Default:OFF)
DIP Switch 7 [FIRMWARE]
SettoONwhenupgradingrmwareversion,and
OFFtoprohibitupdate.(Default:ON)
DIP Switch 8 [CONFIG]
Set to ON when transferring set data from a PC,
andtoOFFtoprohibitsetdatatransfer.(Default:
ON) (For more information on set data transfer,
refer to "Transferring Data Edited by PC between
the VM-3000VA and a PC" in the separate
software manual.)
41. BGM/Paging Recording Output Terminals
[REC OUT BGM/PAGING]
(VM-3240VA and VM-3360VA only)
OutputBGMandPagingbusaudiosignals.
42. Status Output Terminals [STATUS OUT]
Provide the following status outputs in
synchronizationwithunitoperation:
• Emergency status output
• Failure status output
• CPU OFF status output
43. BGM 1 & 2 Input Terminals [BGM 1, 2]
(VM-3240VA and VM-3360VA only)
ConnecttheBGMsoundsource.(–10dB*,10kΩ)
*
0dB=1V
44. Emergency Control Input Terminals 1 – 6
[EMERGENCY CONTROL, IN 1/IN 2]
Connect to an automatic re alarm system and
activate emergency broadcasts, play back/stop
automatic emergency announcements and reset
emergency broadcasts.
Contactinputs1-5areno-voltagemakecontact
inputs.
Input 6 is an isolated voltage input which activates
when the polarity of the applied voltage (24 V
DC is kept applied to this terminal under normal
condition) is reversed.
45. DS Link Connector [DS LINK]
Connects to the VX-2000DS Emergency Power
Supply’sDS-SFlinkconnector.
46. Not used.
47. Audio Input Terminals 1 – 3 [INPUT 1 – 3]
(VM-3240VA and VM-3360VA only)
Electronically-balanced600Ω,–10dB*/–50dB,
XLR/phone jack combination connectors. LINE
or MIC input can be selected, and the phantom
power supply turned on and off. (Refer to "Inputs
1 – 3 Settings" on p. 88.) These inputs can be
converted into transformer-balanced terminals
using the optional IT-450 transformer. It is also
possibletochangemicrophonesensitivityto–30
dB.(RefertotheseparateInstallationguide.)
*
0dB=1V
48. PA Link Connector [PA LINK]
Can be connected to the SX-2000 series when
theVP-200VX(PowerAmplierInputModule)is
installedinsidetheVMamplier.
For the module installation, refer to the separate
InstallationGuideforVM-3000Series.
49. AC Inpu t
Connects to an AC outlet using the supplied AC
power cord.
50. Attenuator Control Outputs [ATT CTRL]
Connecttoexternalattenuators.
51. Direct Output Terminals [DIRECT OUT 100 V
LINE]
These speaker output terminals (100 V line)
provide direct output of paging calls.
52. 24 V DC Output [24 V, +, –]
Provide24VDCoutput,max.0.3A.
Bekijk gratis de handleiding van Toa RM-300MF, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.
Productinformatie
| Merk | Toa |
| Model | RM-300MF |
| Categorie | Niet gecategoriseerd |
| Taal | Nederlands |
| Grootte | 19502 MB |
Caratteristiche Prodotto
| Gewicht | 1100 g |
| Breedte | 200 mm |
| Diepte | 82.5 mm |
| Hoogte | 215 mm |
| Kleur behuizing | Wit |