MIX 2 series RMG 8 T / RME 8 T actuators
5.3.6.5 The "Safety Wind/Rain/Frost" parameter page
Table 27
Designation
Values
Description
Priority of safety objects
1. Wind 2. Rain, 3. Frost
1. Wind, 2. Frost, 3. Rain
1. Rain, 2. Wind, 3. Frost
1. Rain, 2. Frost, 3. Wind
1. Frost, 2. Wind, 3. Rain
1. Frost, 2. Rain, 3. Wind
If wind, rain and frost alarm occur
together, the parameters of the object
with the highest priority will be
implemented.
Example:
1. Rain, 2. Frost, 3. Wind
The parameters with priority 1 apply,
i.e. Start and End of Safety rain.
If the rain alarm (Priority 1) is cancelled,
the parameters for the object with
priority 2 apply, here
Frost - Start.
If the object with priority 2 is also
cancelled, the one with priority 3
applies.
Monitor safety objects
cyclically
no
No monitoring.
After mains failure the safety object will
be reset to 0.
every 10 min
every 20 min
every 60 min
Safety objects that do not receive any
telegrams within the time set here will
be handled as if they had received an
ON telegram and trigger an alarm
(e.g. WIND, etc.).
The sender of the safety telegrams (e.g.
weather station) must transmit them
cyclically.
Max. cycle time = Monitoring time/2
Example:
Monitoring time = every 20 minutes,
cyclical transmission time = 10 min or
less.
Version: May-14 (Subject to change) Page 58 of 87