MIX 2 series RMG 8 T / RME 8 T actuators
5.3.6.3 The "Drive settings" parameter page
Table 25
Designation
Values
Description
Direction of drive run
normal
Standard setting:
Hanging moves from top to bottom.
inverted
For special applications or quick fix for
wrongly wired devices (up/down
directions mixed up).
Complete runtime Down
(s)
Manual input
5 .. 500
Only available when Drive runtime
setting = via ETS.
Enter the measured runtime for
descending (in seconds).
Runtime adjustment for
ascent (s)
Manual input
-15 .. +15
Enter difference between runtime when
ascending and runtime (in seconds)
when descending.
Correction value = t
Up
– t
Down
Step duration of
Step/Stop object
No steps
250 ms
500 ms
1 s
2 s
3 s
4 s
5 s
6 s
7 s
10 s
Only for roller blinds/awning/general
drive.
This specifies whether or not it should
be possible to adjust the drive in small
steps, and it also specifies the duration
of a single step.
Complete slat turning
4 ... 250 [x100 ms]
4 .. 250
Enter the measured turn time of the slats
in increments of 100 ms.
10 = 10 x 100 ms = 1s
No. of steps for a
complete turn
3 Steps
4 Steps
7 Steps
12 Steps
This specifies the number of individual
steps a complete slat turn is to be
divided into (3 to 12).