Theben RMG 8 T KNX handleiding

87 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 45 van 87
MIX 2 series RMG 8 T / RME 8 T actuators
Continuation:
Designation
Values
Description
Parameter for threshold object Counter value 0..255
Threshold
1..254
Default value = 127
Desired threshold.
Example of NO contact with response
as
switch object = 1:
Switches on when:
Object value > threshold
Switches off when:
Object value = threshold - hysteresis
Hysteresis
1..254
Default value = 5
The hysteresis prevents frequent
switching after small fluctuations in
readings.
Parameter for threshold object Counter value 0..65535
Threshold
1..65534
Default value = 1000
Desired threshold.
Example of NO contact with response
as
switch object = 1:
Switches on when:
Object value > threshold
Switches off when:
Object value = threshold - hysteresis
Hysteresis
1..65534
Default value = 5
Parameter for threshold object EIS5 (e.g. CO
2
, brightness…)
Threshold
Format (-)0.00..99999
0.00..99999
Default value = 20
Desired threshold.
Example of NO contact with response
as
switch object = 1:
Switches on when:
Object value > threshold
Switches off when:
Object value = threshold - hysteresis
Hysteresis
0.00..9999
0.00..9999
Default value = 1
The hysteresis prevents frequent
switching after small fluctuations in
readings.
Version: May-14 (Subject to change) Page 45 of 87

Bekijk gratis de handleiding van Theben RMG 8 T KNX, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkTheben
ModelRMG 8 T KNX
CategorieNiet gecategoriseerd
TaalNederlands
Grootte11185 MB