MIX 2 series RMG 8 T / RME 8 T actuators
5.3.5.8 The "Threshold" parameter page
This side is shown if the Activation of the function by parameter is set to Exceeding threshold.
Table 18
Designation
Values
Description
Type of threshold object
Object type: Percent (DPT
5.001)
Object type: Counter value
0..255 (DPT 5.010)
Object type: Counter value
0..65535 (DPT 7.001)
Object type: EIS5 e.g. CO2,
brightness etc. (DPT 9.xxx)
Value type for threshold.
Response on exceeding
the threshold
Should the channel switch on or off on
exceeding the threshold?
The set type of contact must be taken
into account here.
As switch object = 0
NO contact: the relay switches off if
threshold is exceeded.
Opening contact: The relay switches on
if threshold is exceeded.
As switch object = 1
NO contact: The relay switches on if
threshold is exceeded.
Opening contact: the relay switches off
if threshold is exceeded.
Parameter for Percent threshold object
Threshold
1..99 %
Default value = 50%
Desired threshold.
Example of NO contact with response
as
switch object = 1:
Switches on when:
Object value > threshold
Switches off when:
Object value = threshold - hysteresis
Hysteresis (as %)
1..99 %
Default value = 10%
The hysteresis prevents frequent
switching after small fluctuations in
readings.