MIX 2 series RMG 8 T / RME 8 T actuators
Object 5 "Lock/Release"
Locks the channel function.
Responses to setting and cancelling the lock can be configured if the block function has been
activated (configuration options parameter page).
Object 6 "Call up/save scenes"
Only available if the scene function has been activated (configuration options parameter
page).
This object can be used to save and subsequently call up scenes.
Saving stores the channel status.
It does not matter how this status is produced (whether via switch commands, central objects
or the buttons on the device). The saved status is restored when it is called up.
All scene numbers from 1 to 63 are supported.
Each channel can participate in up to 8 scenes.
The scene that is currently active can be ended with the value 63 (= scene 64).
See appendix: Scenes
Object 7 "Lock scenes/Release scenes "
Locks the scene function with a 1 or a 0 depending on the configuration.
As long as it is locked, scenes cannot be saved or called up
Object 8 "Priority on safety"
Priority on safety will be used when the roller blinds or sun protection devices must remain
stationary in an end position for a certain time, e.g. for window cleaning.
This operating mode has the highest priority level.
While priority on safety is active, all operating commands (UP/DOWN, % Height, Step/Stop,
Slat %), the other safety objects and the manual operation will be ignored.
Value obj. 8
Priority on safety
0
inactive
1
2
UP
3
DOWN
Priority on safety is ended with a 1 or a 0.
Version: May-14 (Subject to change) Page 26 of 87