MIX 2 series RMG 8 T / RME 8 T actuators
Continuation:
No. Object name Function
Type
DPT
Flags
C
R
W
T
33 RMG 8 T channel C4 Call up/save scenes
1 byte
18,001
R W T
34
RMG 8 T channel C4 Enable scenes = 1
1 bit
1,003
C R W -
RMG 8 T channel C4 Lock scenes = 1
1 bit
1,003
C R W -
35 RMG 8 T channel C4 Feedback On/Off
1 bit
1,001
C R - T
36
RMG 8 T channel C4 Operating hours feedback
2 byte
7,001
C R W T
RMG 8 T channel C4 Time to next service
2 byte
7,001
C R W T
37 RMG 8 T channel C4 Service required
1 bit
1,001
C R - T
38
RMG 8 T channel C4 Reset operating hours
1 bit
1,001
C R W -
RMG 8 T channel C4 Reset service
1 bit
1,001
C R W -
RMG 8 T channel C4 Switching with priority
2 bit
2,001
C R W -
40
RMG 8 T channel C5 Switch object
1 bit
1,001
C R W -
RMG 8 T channel C5 Threshold 0..255
1 byte
5,010
C R W -
RMG 8 T channel C5 Threshold 0..65535
2 byte
7,001
C R W -
RMG 8 T channel C5 Threshold EIS 5 (DPT9.xxx)
2 byte
9.xxx
C R W -
RMG 8 T channel C5 Threshold as percent
1 byte
5,001
C R W -
41
RMG 8 T channel C5 Logic input in OR gate
1 bit
1,001
C R W -
RMG 8 T channel C5 Logic input in AND gate
1 bit
1,001
C R W -
RMG 8 T channel C5 Logic input in XOR gate
1 bit
1,001
C R W -
42 RMG 8 T channel C5 Lock
1 bit
1,003
C R W -
43 RMG 8 T channel C5 Call up/save scenes
1 byte
18,001
C R W T
44
RMG 8 T channel C5 Enable scenes = 1
1 bit
1,003
C R W -
RMG 8 T channel C5 Lock scenes = 1
1 bit
1,003
C R W -
45 RMG 8 T channel C5 Feedback On/Off
1 bit
1,001
C R - T
Version: May-14 (Subject to change) Page 12 of 87

Bekijk gratis de handleiding van Theben RMG 8 T KNX, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkTheben
ModelRMG 8 T KNX
CategorieNiet gecategoriseerd
TaalNederlands
Grootte11185 MB