MIX 2 series RMG 8 T / RME 8 T actuators
Continuation:
No. Object name Function
Type
DPT
Flags
C
R
W
T
21
RMG 8 T channel C3 Logic input in OR gate
1 bit
1,001
C R W -
RMG 8 T channel C3 Logic input in AND gate
1 bit
1,001
C R W -
RMG 8 T channel C3 Logic input in XOR gate
1 bit
1,001
C R W -
22 RMG 8 T channel C3 Lock
1 bit
1,003
C R W -
23 RMG 8 T channel C3 Call up/save scenes
1 byte
18,001
C R W T
24
RMG 8 T channel C3 Enable scenes = 1
1 bit
1,003
C R W -
RMG 8 T channel C3 Lock scenes = 1
1 bit
1,003
C R W -
25 RMG 8 T channel C3 Feedback On/Off
1 bit
1,001
C R - T
26
RMG 8 T channel C3 Operating hours feedback
2 byte
7,001
C R W T
RMG 8 T channel C3 Time to next service
2 byte
7,001
C R W T
27 RMG 8 T channel C3 Service required
1 bit
1,001
C R - T
28
RMG 8 T channel C3 Reset operating hours
1 bit
1,001
C R W -
RMG 8 T channel C3 Reset service
1 bit
1,001
C R W -
RMG 8 T channel C3 Switching with priority
2 bit
2,001
C R W -
30
RMG 8 T channel C4 Switch object
1 bit
1,001
C R W -
RMG 8 T channel C4 Threshold 0..255
1 byte
5,010
C R W -
RMG 8 T channel C4 Threshold 0..65535
2 byte
7,001
C R W -
RMG 8 T channel C4 Threshold EIS 5 (DPT9.xxx)
2 byte
9.xxx
C R W -
RMG 8 T channel C4 Threshold as percent
1 byte
5,001
C R W -
31
RMG 8 T channel C4 Logic input in OR gate
1 bit
1,001
C R W -
RMG 8 T channel C4 Logic input in AND gate
1 bit
1,001
C R W -
RMG 8 T channel C4 Logic input in XOR gate
1 bit
1,001
C R W -
32 RMG 8 T channel C4 Lock
1 bit
1,003
C R W -
Version: May-14 (Subject to change) Page 11 of 87