4.2.1 Installation Environment Requirements
• If the inverter is installed in a place with lush vegetation, weed on a regular basis. In ad-
dition, the ground beneath the inverter needs to undergo certain treatment, such as lay-
ing cement or gravel, etc. (an area of 3m×2.5m is recommended).
• Do not install the inverter in an environment with flammables, explosives, or smoke.
• Do not install the inverter in places prone to water leak, e.g., under the air-conditioner
vent, the air vent, or the cable outlet window of the machine room, so as to prevent de-
vice damage or short circuit caused by intrusion of water.
• Do no install the inverter in a place with corrosives such as corrosive gas and organic
solvent, etc.
• When the inverter is running, its surface may carry high voltages or get very hot. Do not
touch it; otherwise, it may lead to burns or electric shocks.
• Do not install the inverter in a place that is easy to reach for people.
User Manual 4 Mechanical Mounting