No. Name
E ACB: Air circuit breaker
F Fuse
NOTICE
ACB can only be closed when there is a lock, and the lock cannot be pulled out after
closing.
3.4.2 Main Parts of Transformer
The transformer room mainly includes a transformer inside.
Figure
Name Description
Oil filling valve
when oil level of the MV transformer oil tank is
low, open the valve for oil filling.
Pressure Relief
Valve
The valve automatically releases when the oil
pressure inside the oil tank reaches 55kPa.
Oil Level Indicator
The MV transformer will stop operating if the
oil level falls below the lowest scale on the oil
level indicator or below the oil level scale
required for safe operation of the transformer.
When the oil level is excessively high, open
the drain valve to lower the oil level.
When the oil level is excessively low,
disconnect the transformer and check the oil
tank for leakage.
Oil Temperature
Indicator
The alarm temperature is set to 95. When
the oil temperature reaches the value, alarm
signals will be sent to the intelligent power
distribution cabinet or a communication unit
provided by the customer.
The tripping temperature is set to 100.
When the oil temperature reaches the value,
tripping signals will be sent to the intelligent
power distribution cabinet or a communication
System Manual3 Product Description
14