Before operation, the two fixing bolts between the corner pieces of the pressure relief door
on the back of the lv cabinet and the back plate need to be removed. The positions of the
fixing bolts are shown in the following figure:
During normal operation, ensure that the pressure relief door is closed.
When maintenance of the MV Station involves dismantling the back panel,
ensure that the pressure relief door is closed after the maintenance is
completed.
f there is a short circuit or arc inside the low-voltage cabinet, after repairing the
fault, check and close the pressure relief door. If the pressure relief door is
severely deformed, contact the SUNGROW for replacement.
Internal Structure
Take MVS9000 LV cabinet as an example, internal structure shows the figure below.
The figure above is indicative only, and actual product may differ.
No.
Name
A Communication and distribution terminals
B Disconnector
C Branch fuse
D LV wiring terminals
System Manual 3 Product Description
13