Sungrow MVS4500-LV handleiding

97 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 56 van 97
If the single-core cables exceed 400 meters, log into the Web UI of Logger4000, on the
MPLC page, set the PLC master node's frequency to Band2 or Band3.
Requirements for parallel-pair cables
When using parallel-pair cables, to ensure MPLC communication quality, the length
difference between the two sets of cables must not exceed 5 meters. For single-core
parallel-pair, the requirements for both sets of cables and the frequency band settings are
the same as mentioned above.
6-14 Parallel-pair cables layout
PLC cable installation requirements
The distance between low-voltage AC cables and medium-voltage AC cables should
meet the following requirements:
- Maintain a minimum horizontal distance of 0.5m between low-voltage AC cables and
medium-voltage AC cables when laid parallel.
- If two cables are laid in a crossing manner, the angle of crossing should be between
60° and 120°, and the vertical distance should be no less than 0.5m.
System Manual 6 Electrical Installation
51

Bekijk gratis de handleiding van Sungrow MVS4500-LV, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSungrow
ModelMVS4500-LV
CategorieNiet gecategoriseerd
TaalNederlands
Grootte9056 MB