Sungrow MVS4500-LV handleiding

97 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 45 van 97
Figure 6-3 Single splicing cables
Table 6-2 Requirements
Name Cable specifications Cable outer diameter
Single core cable
Maximum 400mm
2
≤ 35 mm
Three-core cable
Maximum 3×400mm
2
50 mm to 78.5 mm
Figure 6-4 Double splicing cables
Table 6-3 Requirements
Name Cable specifications Cable outer diameter
Single core double splicing
cable
Maximum 185mm
2
≤ 26 mm
Three-core double splicing
cable
Maximum 3×185mm
2
42 mm to 50 mm
Wiring Distance Requirements
The following figure (1) shows the distance between adjacent branches after connecting a
single splicing cable, while figure (2) shows the requirement for three-phase distance.
System Manual6 Electrical Installation
40