TROUBLESHOOTING - EVAPORATOR SYSTEM*
CONDITION TROUBLESHOOTING
Low Suction Pressure Check if sight glass is flashing or showing low charge.
Check that expansion valve (TXV) isnt restricted. Check element charge.
Check that refrigeration lines and/or hoses are not kinked on either high or
low sides.
Check that evaporator fan motors are working.
Check that superheat is between 6 °F to 8 °F.
Check that there is no air recirculation around evaporator coil.
Check that evaporator coil is not iced up.
High Suction Pressure Check for refrigerant overcharge.
Compressor reed valves may be faulty. Check for high suction pressure /
low head pressure. If pressure is out of range, perform pump down.
Check that the cooling loadisnt high. Product must be pre-chilled before
placing in refrigerated section of case.
Check that unit is not exposed to direct sunlight via windows or any other
heat source (ovens, fryers, etc.).
Check that superheat adjustment isnt low.
Check TXV bulb installation
a. Poor thermal contact.
b. Warm location.
*This Service Is To Be Performed By Trained Service Providers Only