CONDITION TROUBLESHOOTING
Case Not Lining
Up
See Installation Section for instructions on properly aligning case (alongside other
cases) and adjusting levelers.
Water Is On The
Floor
Caution! Water on flooring can cause much damage! Until cause is determined
(and repaired), follow these procedures:
• Use wet-dry vacuum (or mop & bucket) to remove standing water.
• Use ‘catch pans’ for water to drain into. Swap out regularly until case has
completely drained.
Check that the drain trap is free of debris.
Check that the drain hose is correctly positioned over condensate pan (or floor drain,
for remote units).
Check store conditions. To prevent condensation in Type 1 condition environments,
maximum conditions are to be 55% humidity / 75 °Fahrenheit. For Type 2 condition
environments, maximum conditions are to be 60% humidity / 80 °Fahrenheit. See
serial label (at case rear near main power switch) for Type of your case.
Check condensate pan float for proper operation (heat rod condensate system only).
Check that condensate pan is properly plugged in or connected.
Caution! Condensate pan may be malfunctioning (electrical heat rod condensate
system). If so, water will overflow pan and seep onto flooring causing damage! Until
condensate pan is functioning (or is replaced), follow these procedures:
• Use wet-dry vacuum (or mop & bucket) to remove standing water.
• Use ‘catch pans’ for water to drain into. Swap out regularly until case has
completely drained.
Caution! Disruption of power can cause water to overflow pan and seep onto
flooring causing damage! Check that power to case is constant. Until power is
restored, follow these procedures:
• Use wet-dry vacuum (or mop & bucket) to remove standing water.
• Use ‘catch pans’ for water to drainage. Swap out regularly until evaporation of
case is complete (or until power is restored).
• When power to case is restored, condensate pan should function properly and
water will no longer overflow onto flooring.
Caution! Wicking material may be dirty or worn and need replacement (hot gas
condensate system only).
• Slide refrigeration system out from under unit.
• After refrigeration system has been carefully slid out from under unit, replace
wicking material with new. If wicking material is not available, contact Structural
Concepts®. See toll-free number at last page of this operating manual.
TROUBLESHOOTING (TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY) - PAGE 1 of 3