accesses one of the 4 setting menus. Confirm by pressing the button [16]. If the
password entered is invalid, the appliance will revert to normal operation.
PASSWORD = 3
Displayed
message
Parameter
designation
Function
(setting range)
Factory setting
ALH
Temperature
deviation: upper
temperature
limit alarm
The alarm is triggered if
the actual temperature
value measured exceeds
the total of the
temperature setting and
temperature variation.
(0 – 100
o
C)
5
o
C
ALL
Temperature
deviation: lower
temperature
limit alarm
The alarm is triggered if
the actual temperature
value measured is below
the difference of the
temperature setting and
temperature variation.
(0 – 100
o
C)
0
o
C
P
PID control
proportional
parameter
Parameter auto control
(0.1 – 300
o
C)
10
o
C
I
PID control
integral
parameter
(1 – 2000)
d
PID control
differential
parameter
(0 – 1000)
T
Control cycle
The time interval
between the heating
system control cycles
(1 – 30) seconds
Pb
Temperature
deviation
control
Usually used to offset low
temperature deviations
Pb = actual temperature
– measured temperature
(-50 – 50
o
C)
0
o
C
PL
Temperature fall
offset
Usually used to offset
high temperature
deviations
PL = 1000 x (actual
temperature – measured
temperature) / measured
temperature
(-999 – 999)
0
Addr
Address number
(1 – 32)
1