The following table shows the mode to proceed to detect and resolve any incidents shown:
Alarm
number
Alarm text Description Alarm
type
1
Run Error Supply Air Fan Malfunction of supply air fan A
6
Change Filter Prefi lter % Filter need replacement C
10
Fire Alarm Fire alarm activated C
11
Remote off active Remote On/Off active A
23
Electric heating is overheated Electric Heater Thermal protectors activated C
24
Frost risk Frost protection function is overriding the control
of the water heater output
C
25
Water temp too low, system off Water temperature below frost limit value (<7ºC) A
27
Sensor error outdoor temp Malfunction of outdoor air temperature sensor C
41
Manual heater control The electric heater is in manual mode C
42
Manual exchanger control Heat exchanger output in manual control C
43
Manual cooler control Cooling output is in manual control A
48
Internal battery error Internal battery needs replacing A
49
Sensor error Supply Air temp Malfunction of supply air temperature sensor A
50
Sensor error Extract Air temp Malfunction of extraction air temperature sensor A
55
Sensor error SAF pressure Malfunction of supply air pressure sensor A
58
Sensor error Frost Protection temp Malfunction of water temperature sensor C
90 Change External Filter Extraction Air Filter needs replacement
(&.;C;H=;D9OEF;H7J?EDI
If any problems are noted on the unit, turn it off using the emergency shut-off device.
These emergency operations will generally be the result of some problem with the elec-
trical circuit, in which case you may have problems with the motors. You will therefore
need to disconnect the power to locate the fault, which may be inside the unit (short
circuit) or external to it (problems with the power supply, voltage variations, etc.).
In the event of fire, it must be extinguished using suitable extinguishers. Extinguishers
should be appropriate for use on electrical fires.
('.FH;L;DJ?L;C7?DJ;D7D9;
Preventive maintenance is a preset programme of checks that is followed regularly to
prevent equipment breakdowns.
The supplemental Building Facility Technical Regulations are applicable at all times to
maintenance standards, except when justified otherwise for technical reasons.
The maintenance supervisor should keep a copy of the preventive maintenance recom-
mendations given below on file, making as many copies as needed for use.
According to the equipment’s operating needs, it is crucial to make a list of those ele-
ments that are needed to quickly resolve equipment faults. This list will serve to deter-
mine the spare parts inventory needed to be able to perform repairs quickly.