Triac controller for proportional control
of electric heating
PULSER/D is a proportional controller for electric heating with
automatic voltage adjustment. PULSER/D pulses the whole load
On - Off. The ratio between On-time and Off-time is varied 0 - 100%
to suit the prevailing heat demand. The current is always switched at
zero phase angle to prevent RFI.
PULSER/D is only intended for electric heating control. The control
principle makes it unsuitable for motor- or lighting control.
PULSER/D cannot control 3-phase loads.
PULSER/D is intended for DIN-rail mounting.
Installation
Mount PULSER/D on a DIN-rail in a cabinet or other enclosure.
Mount PULSER/D vertically with the text right side up.
Protection class: IP20
Ambient temperature: 0 - 40°C
PULSER/D emits approx. 20W of heat which must be
dissipated.
Wiring
Supply voltage (g 1)
Terminals 1 and 2. Not polarity sensitive.
Supply voltage: 200 - 415V AC, 50 - 60 Hz with automatic voltage
adjustment.
Maximum current 16A.
The supply voltage to PULSER/D should be wired via an all-
pole switch with a minimum contact gap of 3mm. PULSER/D must
be earthed.
Load (g 1)
Terminals 3 and 4.
Resistive single- or two-phase heater.
Maximum load: 3680W at 230V (16A)
6400W at 400V (16A)
Minimum load: 230W at 230V (1A)
400W at 400V (1A)
External sensor and setpoint (gs 2 - 6)
Terminals G1, G2 and G3. Not polarity sensitive.
The choice of terminals is determined by whether the inter-
nal setpoint is to be used or not.
If the internal setpoint is to be used the sensor is to be connect-
ed to terminals G1 and G3.
If an external setpoint device is used, use terminals G1 and G2.
The PULSER/D sensors have high potential compared to
neutral and earth (>200V). Thus, wiring and installation of the
sensors must comply with local codes for line voltage installa-
tions.
Night set-back (g 7)
Terminals G1 and K. Voltage-free closure will give a 5K night set-
back.
Figures
Fig 1: Wiring of supply voltage and heater.
Fig 2: Wiring of room sensor TG-R530 when using internal set-
point.
Fig 3: Wiring of room sensor TG-R430 used as external setpoint
and sensor.
Fig 4: Wiring of oor or duct sensor when using internal setpoint.
Fig 5: Wiring of external separate sensor when using TG-R4xx
as external set-point.
Fig 6: Wiring of external, separate sensor when using potentio-
meter TBI-xx as external setpoint.
Fig 7: Wiring of night set-back function.
Control principle
PULSER/D pulses the full load On - Off. PULSER/D adjusts the
mean power output to the prevailing power demand by propor-
tionally adjusting the ratio between On-time and Off-time. The
pulse period (=the sum of On-time and Off-time) is xed 60
seconds.
PULSER/D has zero phase-angle ring to eliminate RFI.
PULSER/D automatically adjusts its control mode to suit the con-
trol object dynamics.
For rapid temperature changes e.g. supply air control
PULSER/D will act as a PI controller with a proportional band of
20K and a reset time of 6 minutes.
For slow temperature changes e.g. room control PULSER/D will
act as a P controller with a proportional band of 1.5K.
i
Consult documentation in all
cases where this symbol is
used, in order to nd out the
nature of the potential hazards
and any actions to be taken
Read this instruction before
installation and wiring of the
product
88
59 115
PULSER/D
16 A 210 - 415 V ~