MODBUS MAP (continuation)
INPUT REGISTERS (read only) continuation
Modbus
Address
Input register Data
type
Range Def. Observations
30019 OverVoltage_Alarm_Count 16bits 0-65535 - Overvoltage alarm counter
30020 ShortCircuit_Alarm_Count 16bits 0-65535 - Short circuit alarm counter
30021 Current_Alarm_Count 16bits 0-65535 - Motor current alarm counter
30022 TempPCB_Alarm_Count 16bits 0-65535 - PCB temperature alarm counter
30023 TempIPM_Alarm_Count 16bits 0-65535 - IPM temperature alarm counter
30024 FOC_Alarm_Count 16bits 0-65535 - FOC control alarm counter
30025 OpenPhase_Alarm_Count 16bits 0-65535 - Motor phase error alarm counter
30026 Minutos_ON 16bits 0-1440 - Minutes operation of powered motor
30027 Days_ON 16bits 0-65535 - Days operation of powered motor
30028 Minuts_Running 16bits 0-1440 - Minutes operation with motor running
30029 Days_Running 16bits 0-65535 - Days operation with motor running
30030 MSB_Motor_Start_Count 16bits 0-65535 - Motor starts MSB
Example: MSB = 2 = 2 x 65,535 = 131,070 starts + LSB
30031 LSB_Motor_Start_Count 16bits 0-65535 - Motor starts LSB
Example: LSB = 1000 = 1,000 starts + MSB
HOLDING REGISTERS read and edit)
Modbus
Address
Holding register Data
type
Range Default Observations
40002 Address 16bits 1-247 1 Modbus Channel/Direction
40003 Baud Rate 16bits 48: 4800
96: 9600
192: 19200
384: 38400
192 Bus speed
40004 Parity 16bits 0: EVEN
1: ODD
2: Non parity
0 Parity
40005 Motor_Max_Speed 16bits 0-5000 Ex-factory
maximum
speed
Maximum motor speed. Values outside the ex-factory limits or
lower than Holding register 40006 are not accepted
40006 Motor_Min_Speed 16bits 0-5000 Ex-factory
minimum
speed
Minimum motor speed. Values outside the ex-factory limits or
higher than Holding register 40005 are not accepted
40007 Motor_Max_Cu-
rrent
16bits 0-10000 Ex-factory
maximum
intensity
Maximum motor intensity (mA), doesn't accept values higher
than the ex-factory limit
40008 FG 16bits 0-10 1 Tachometer pulses
40009 Slave_Enable 16bits 0: OFF
1: ON
1 Slave function to control a second fan
40010 Slave_Offset 16bits -20-20 0 Offset of the slave setpoint with respect to the setpoint (%)
40011 AN_IN1_1V/5.5mA 16bits -64000 Ex-factory
maximum
speed
Equivalence in real units of 1V or 5.5mA with respect to input IN1
Note: Only used for constant power, constant torque, PI, Proportio-
nal and Min/Max operating modes
40012 AN_IN1_9.5V/19mA 16bits -64000 Ex-factory
minimum
speed
Equivalence in real units of 9.5V or 19mA with respect to input
IN1
Note: Only used for constant power, constant torque, PI, Proportio-
nal and Min/Max operating modes
40013 AN_IN1_Filter 16bits 0: EVEN
1: LOW
2: MEDIUM
3: HIGH
1 Degree of fi ltration of input IN1. A high degree favours progres-
sive changes in fan speed
40014 AN_IN2_0V/4mA 16bits -64000 0 Equivalence in real units of 0V or 4mA with respect to input IN2
40015 AN_IN2_10V/20mA 16bits -64000 0 Equivalence in real units of 10V or 20mA with respect to input
IN2
40016 AN_IN2_Filter 16bits 0: EVEN
1: LOW
2: MEDIUM
3: HIGH
1 Degree of fi ltration of input IN2. A high degree favours progres-
sive changes in fan speed
40018 Set_Point_Input 16bits 0: AN_IN1
1: MODBUS
0 Setpoint control
40019 Modbus_Set_Point 16bits 0-65535 0 Setpoint via Modbus, units according to Holding register 40017
operating mode
Note: If holding registers 40011 and 40012 are not completed, the
units will be mV
40025 Factory_Reset 16bits -64000 0 Write 1234 to reset motor and return to factory settings
Note: By factory values we mean the limits corresponding to the maxi-
mum performances, constant speed operating mode and adjustment
via IN1. If the unit came with a special confi guration, this will be lost

Bekijk gratis de handleiding van Soler & Palau HXBR ECOWATT, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.