Soler & Palau DUOVENT MODULAR DV handleiding

46 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 21 van 46
Ventilation units with heat recuperation
DUOVENT
®
MODULAR DV/RV
21
After gluing the seal, place the blocks as close to each other as possible and connect the blocks using the connecting elements on the end
profiles of the unit so that the blocks fit tightly together. Use the supplied M8x25 screws for the connection (24 pieces included in total).
Each connecting element contains
a total of 2 M8 threads
for 2 pcs of M8 screws
Each block No. 1 and No. 3 is provided with a total of 6 pieces of connecting elements in each connecting plane.
The middle block No. 2 is equipped with a total of 12 pieces of connecting elements.
If the unit is equipped with the ROOFPACK accessory, it is necessary to connect the roof parts of the unit in the connecting planes of the
blocks. Is it necessary to use the enclosed rivets Ø 4 mm and connecting strips to connect the roofs, which are pre-assembled on the individual
blocks.
roof connecting strip
Before connecting the unit to the HVAC piping, check the markings and directions of the air flow in the unit. Marking of air currents ODA
/ SUP / ETA / EHA - see. chap. 3.2.
Always follow the markings and directions of airflows that are marked on the stickers on the outer casing of the unit.
The unit must be connected to the piping via flexible sleeves to prevent the transmission of vibrations to the air distribution systems. The
flexible sleeves must be bridged by a flexible conductive connection for the discharge of static electricity from the device. If the elastic cuffs
are secured with spacers against damage during transport and storage, these can be removed only after the attachment of both flanges, on
the one hand to the unit and on the other to the air distribution systems.
The unit is equipped with integrated connection flanges for connection to air ducts. The spacing of corner holes with M8 threads is adapted for
P30 flanges (the height of the air flange flange is 30 mm).
strip P30
detail of the flange profile of the
connecting HVAC piping
30

Bekijk gratis de handleiding van Soler & Palau DUOVENT MODULAR DV, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.

Productinformatie

MerkSoler & Palau
ModelDUOVENT MODULAR DV
CategorieNiet gecategoriseerd
TaalNederlands
Grootte14752 MB