Boost/High airflow:
Setting of the high/boost ½ hour temporized airflow.
Enter with the key choose the airflow value with the keys , then confirm with the
key .
Low airflow air quality sensor*:
Setting of the minimum airflow.
Enter with the key choose the airflow value with
the keys ,
then confirm with the key .
Free cooling airflow:
Having avoided the heat exchanger, the 100% by-pass system of the IDEO allows the
introduction of cooler fresh air in the night without it being warmed by the warm air
accumulated in the house during the day.
This system works automatically with this conditions:
- inner >1+ outer and inner > 24ºC and outer> 12ºC,
The specific airflow can be adjusted to optimize the cooling nigh time or free cooling (see
paragraph 5-1-a)
If you want , you can manually switch on the by-pass mode for a period of 8 hours, by
pressing the by-pass button. During this operation it is possible to cancel this function by
pressing the by-pass key once more.
Enter with the key choose the airflow value with the keys , then confirm with the
key .
High airflow air quality sensor*:
Setting of the maximum airflow.
Enter with the key choose the airflow value with
the keys ,
then confirm with the key .
Minimum voltage of the air quality sensor*:
Setting of the minimum voltage.
Enter with the key choose the voltage value with
the keys ,
then confirm with the key .
Maximum voltage of the air quality sensor*:
Setting of the maximum voltage.
Enter with the key choose the voltage value
with the keys ,
then confirm with the key .
Qmin.
Qmax.
Umin.
Umax.
Airflow (m
3
/h)
Tension (v)
Working chart of the
Air Quality sensor (0-10V)*
*: Humidity, CO2, VOC sensor.
Automatic By-pass:
You can activate or deactivate the automatic function for the by-pass.
Enter with the key , choose activate (ON) or deactivate (OFF) with the keys ,
then confirm with the key .
If it is deactivated, you can always switch on the bypass with the remote control.
Text Automatic By-pass:
You can modify the outdoor bypass activation temperature.
Factory setting: +12ºC
Setting range: +11 +20ºC
Enter with the key , modify the temperature with the keys ,
then confirm with the key .
Low airflow:
Setting of the low airflow/low speed.
Enter with the key choose the airflow value with the keys , then confirm with the
key .