ECO 120 / ECO 121 - Alarm thermometer
Operation
B-H86.0.0X.DK2-4.1 Page 10 of 22
4 Operation
4.1 Opening the configuration menu
1 Press the Function key for 2 seconds to open the Configuration menu.
2 (ONF appears in the display. Release the Function key.
Parameter
Values
Meaning
AL.
Alarm
OFF
No alarm active
ON
Alarm via text insertion, acoustic signal and flashing
of the background lighting
BEEP
Alarm via text insertion and acoustic signal
L,TE
Alarm via text insertion and flashing of the back-
ground lighting
AL.LO
Min. alarm limit (only available if AL <> off)
-70.0 .. AL.X,
a min. alert is triggered if the value falls below this
value. (at °F: -94.0 .. AL.Hi)
-200.0 .. AL.X,
a min. alert is triggered if the value falls below this
value. (at °F: -328.0 .. AL.Hi) (at ECO 120)
AL.XI
Max. alarm limit (only available if AL <> off)
AL.LO .. 250.0
If the value is exceeded, a max. alarm is triggered.
(at °F: AL.Hi .. 482.0)
AL.LO .. 450.0
If the value is exceeded, a max. alarm is triggered.
(at °F: AL.Hi .. 842.0) ) (at ECO 120)
POFF
Shut-off time
OFF
No automatic shut-off
15, 30, 60, 120, 240
Automatic shut-off after a selected time in minutes,
during which no buttons have been pressed