Start-up (TE)
When the unit is used for the first time or after a
long period of non-use, smoke or an odour may
result from dust or dirt which has collected on the
element. This is completely normal and disappears
after a short time.
Control options
Stepless airflow control with door contact/position
limit switch
When the door is closed the fan runs at low speed.
When the door opens, the fan runs at high speed,
set on the remote control or the control panel at
the gable end.
See Figure 2 and Accessories pages.
Adjustment of the air curtain and airflow
The direction and speed of the airflow should be
adjusted considering the load on the opening.
Pressure forces affect the airstream and force it
inwards towards the premises (when the premises
are heated and the outdoor air is cold).
The airstream should, therefore, be directed
outwards to withstand the load. Generally
speaking, the higher the load, the greater the
angle required.
Service, repairs and maintenance
For all service, repair and maintenance first carry
out the following:
1. Disconnect the power supply.
2. The front hatch is removed by removing the
screws on the top of the unit and then detach
the bent edge at the bottom. (Fig.3)
3. After the service, repair and maintenance
reattach the front hatch. Place the hatch at the
lower edge with the bent edge and fasten on
top with screws.
Note that when carrying out work where the end
is removed, the outlet grille also detaches.
Basic setting fan speed
The fan speed when the door is open is set
using the control. Note that the airflow direction
and the fan speed may need fine adjustment
depending on the loading of the door.
The largest cable diameter for the terminal block
is AWG6. The cable glands used must meet the
protection class requirements. In the distribution
board it is to be indicated that ”the air curtains can
be supplied from more than one connection”.
See wiring diagrams.
NOTE: Care must be taken when connecting the
pipes. Use a pipe wrench or a similar tool to grip
the air curtain connections to prevent straining of
the pipes and subsequent water leakage during
connection to the water supply pipe-work.
Overheating
The air curtain unit with electrical heating is
equipped with an overheat protection. If it is
deployed due to overheating, reset as follows:
1. Disconnect the power supply with the isolator
switch.
2. Determine the cause of overheating and rectify
the fault.
3. Remove the front hatch.
4. Press the red button located inside the air
curtain unit, at the inner gable of the terminal
box.
5. Reattach the front hatch and connect the unit
again.
All motors are equipped with an integral thermal
safety cut-out. This will operate, stopping the air
curtain should the motor temperature rise too
high. The cut-out will automatically reset when
the motor temperature has returned to within the
motor’s operating limits.
Maintenance
Since fan motors and other components are
maintenance-free, no maintenance other than
cleaning is necessary. The level of cleaning can
vary depending on local conditions. Undertake
cleaning at least twice a year. Inlet and exhaust
grilles, impeller and elements can be vacuum
cleaned or wiped using a damp cloth. Use a
brush when vacuuming to prevent damaging
sensitive parts. Avoid the use of strong alkaline or
acidic cleaning agents.