26 Filling / Recovery function
"Measurements / Tests" menu is displayed.
Press OK on "Filling / Recovery" line.
Press OK to conrm the refrigerant used or select the required one by pressing
Press OK on "Mode" line and select "Filling" mode.
Enter the target value on "Target Value" line between 0 and 110 kg.
Press OK on Next.
Turn on the Si-RS1 scale.
Connect two wired temperature probes or use wireless probes.
Press OK once the manifold has complete the auto-detection.
Value are displayed on the manifold screen.
Press "Play" before opening the valve on the bottle. After pressing "Play" the test automatically tracks the
delta weight on the Si-RS1, so you can easily see how much refrigerant has been added to the system.
To change bottle press "Pause". When the new bottle is ready press "Play" again and the test continues to
track total delta weight (combining rst and second bottle).
When nishing the test, press "Stop" then "Save" to save the type of refrigerant, time, and amount of refrig-
erant charged in the manifold memory.