ENGLISH
When you install the outdoor unit at wayside, you should install it above 2m height or make sure that the heat from the
outdoor unit shouldn't be in direct contact with passersby. (The ground for application :The revision of regulation for
facility in building by the law of the Ministry of Construction and Transportation.
• You have just purchased a system air conditioner and it has been installed by your installation specialist.
• This device must be installed according to the national electrical rules.
• With an outdoor unit having net weight upper than 60kg, we suggest do not install it suspended on wall, but
considering oor standing one.
CAUTION
When installing the outdoor unit near seashore, make sure it is not directly exposed to sea breeze. If you can not nd a
adequate place without direct see breeze, protection wall should be constructed.
- Install the outdoor unit in a place (such as near buildings etc.) where it can be prevented from sea breeze which can
damage the outdoor unit.
Outdoor unit
Outdoor unit
Sea breeze Sea breeze
Sea
Sea
- If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around to block the sea
breeze.
• Protection wall should be constructed with a solid
material such as concrete to block the sea breeze
and the height and the width of the wall should be
1.5 times larger than the size of the outdoor unit.
Also, secure over 700mm between the protection
wall and the outdoor unit for exhausted air to
ventilate.
Protection wall
Outdoor unit
Sea breeze
Sea
- Install the outdoor unit in a place where water can drain smoothly.
• If you cannot nd a place satisfying above conditions, please contact manufacturer. Make sure to clean the sea water
and the dust on the outdoor unit heat exchanger and spread corrosion inhibitor on heat exchanger. (At least one time
per one year.)
• Depending on the condition of power supply, unstable power or voltage may cause malfunction of the parts or
control system. (At the ship or places using power supply from electric generator, etc).
CAUTION
CAC GD-EU_IM_32793A-23_EN.indd 7 2016-05-25 오후 7:08:24