Installing the circuit breaker and wires
Wiring works
Power supply MCCB ELB Power cable Earth cable Communication cable
Max : 242V
Min : 198V
X A
X A, 30mmA
0.1 sec
2.5mm
2
2.5mm
2
0.75~1.5mm
2
The capacity of ELB, MCCB X[A] = 1.25 X 1.1 X ∑Ai
Decide the capacity of ELB and MCCB by below formula.
Decide the power cable specication and maximum length within 10% power drop among indoor units.
❈
X
: The capacity of ELB, MCCB
❈
∑Ai : Sum of Rating currents of each indoor unit.
❈
Refer to each installation manual about the rating current of indoor unit.
❈
Calculation
- Installing with 1 sort wire
❈
If the terminal input pressure of the indoor unit goes down by more than 10%, install the thicker wire.
- Installing with 2 dierent sort wire
T Coef: 1.55
T Lk: Distance among each indoor unit[m], Ak: Power cable specification[mm
2
]
i
k: Running current of each unit[A]
∑ (
Coef×35.6×Lk×ik
) <
10% of input voltage[V]
1000×A
k
n
k=1
10[A]
Indoor unit10
20[m]10[m]0[m]
9[A] 1[A]
100[m]
MCCB
Indoor unit2Indoor unit1
ELB
Example of Installation
Total power cable length L = 100(m), Running current of each units 1[A]
Total 10 indoor units were installed
Apply following equation.
220[V]
-2.2[V] -2.0[V]
············ 2.5[mm
2
] ············
208.8[V](Within 198V~242V)
-(2.2+2.0+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-11.2[V]
it's okay
2.5[mm
2
] 2.5[mm
2
]
220[V]
-1.4[V] -1.2[V]
············ 2.5[mm
2
] ············
209.5[V](Within 198V~242V)
-(1.4+1.2+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-10.5[V]
it's okay
4.0[mm
2
] 4.0[mm
2
]
∑ (
Coef×35.6×Lk×ik
) <
10% of input voltage[V]
1000×A
k
n
k=1