Refrigerant piping works
Draining form
Flexible hose
Air vent
300mm or less
Horizontal drainpipe
more than 1/100 slope
Within
300~550mm
1~1.5m
200mm
or more
Ceiling
Hanger
20mm
or more
Without the drain pump
With the drain pump
1. Install horizontal drainpipe with a slope of 1/100 or more and x it by hanger space of 1.0~1.5m.
2. Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit.
3. Do not install the drainpipe to upward position. It may cause water ow back to the unit.
1. The drain pipe should be installed within 300mm to 550mm from the exible hose and then lift down 20mm or more.
2. Install horizontal drainpipe with a slope of 1/100 or more and x it by hanger space of 1.0~1.5m.
3. Install the air vent in the horizontal drainpipe to prevent water ow back to the indoor unit.
4. The exible hose should not be installed upward position, it may cause water ow back to the indoor unit.
1~1.5m
Horizontal drainpipe
more than 1/100 slope
Ceiling
Hanger
Flexible hose
• You may not need to install it if there were proper slope in the horizontal drainpipe.