Samsung AR13JPFUPWKNHC handleiding
Handleiding
Je bekijkt pagina 40 van 46

English-40
Installing and connecting the drain hose of the outdoor unit
While heating, ice may accumulate. During the process of defrosting, check if condensation draining is adequate. For adequate
draining, do the following.
1. Insert the drain plug into the drain hole on the underside of the outdoor unit.
2. Connect a drain hose to the drain plug.
3. Ensure that condensation draining is adequate.
Frame
Ground
Estimated
snow fall
Snow-proof hood
Bottom surface of outdoor unit
Drain hose
Drain hole
Drain plug
Drain hole
Drain plug
• Toavoiddrainplugfromcontactingtheground,securegapbetweenthe
ground and the bottom surface of the outdoor unit.
• Inareaswithheavysnowfall,piledsnowcouldblocktheairintake.
To avoid this incident, install a frame that is higher than estimated snow
fall. In addition, install a snow-proof hood to avoid snow from piling on the
outdoor unit.
The outdoor unit is loaded with sucient R-22 refrigerant.
You should evacuate the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it aects the compressor.
It may cause reduction of cooling capacity and malfunction.
• Wheninstalling,makesurethereisnoleakage.Whenrecoveringtherefrigerant,groundthecompressorrst
before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works
with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle
abnormally high. It may cause explosion and injury.
Evacuating the connected pipes
IB&IM_EN_DB98-33330A-08.indd 40 11/3/2015 8:45:41 AM