Handleiding
Je bekijkt pagina 42 van 78

42
Refrigerant pipe installation
English
Installation Procedure
Installing the MCU
MCU specification
Model MCU-S12NEK1N MCU-S8NEK1N MCU-S6NEK2N
Exterior of MCU
Number of connectable indoor units at one port Up to 8 units Up to 8 units Up to 8 units
Maximum number of indoor units (Total) 64 64 32
The maximum capacity of the connectable indoor units
at one port
16 kW 16 kW 16 kW
The maximum capacity of the connectable indoor units at
one port (with Y-JOINT)
32.0 kW 32.0 kW 32.0 kw
The maximum capacity of the connectable indoor units 85.0 kW 85.0 kW 61.6 kW
Internal EEV
Not included
Cannot connect indoor unit without internal EEV
Model MCU-S4NEK3N MCU-S2NEK2N MCU-S1NEK1N
Exterior of MCU
Number of connectable indoor units at one port Up to 8 units Up to 8 units Up to 8 units
Maximum number of indoor units (Total) 32 16 8
The maximum capacity of the connectable indoor units
at one port
16 kW 16 kW 16 kW
The maximum capacity of the connectable indoor units at
one port (with Y-JOINT)
32.0 kw 32.0 kw -
The maximum capacity of the connectable indoor units 61.6 kW 32.0 kW 16 kW
Internal EEV
Not included
Cannot connect indoor unit without internal EEV
CAUTION
• Indoor units without internal EEV(AM****NTDE*, AM****NADE*) can not be connected directly to the MCU.
• Please connect these indoor units using EEV kit(MEV-E**SA, MXD-E**K***A).
• If the sum of the connected indoor unit capacity connected to the MCU is greater than 67.2kW, performance may vary depending on
operating conditions.
• The incoming pipe diameters supplying refrigerant to the MCU are determined based on the sum of the connected indoor units. If
these pipe diameters are different than the MCU pipe diameters, use the provided reducers to connect to the MCU. If the provided
reducers are not the correct size, field supplied reducers must be used.
Installing the indoor units
Model MCU-S12NEK1N MCU-S8NEK1N MCU-S6NEK2N
Example installing
(Each port
connection)
MCU-S4NEK3N MCU-S2NEK2N MCU-S1NEK1N