Installing the unit
IMPORTANT: When installing the unit, always remember to connect rst the refrigerant tubes, then the
electrical lines.
Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product
appears damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the
installer or the authorized technician has collected the material from the retailer.)
After completing the installation, always carry out a functional test and provide the instructions on how to
operate the air conditioner to the user.
Do not use the air conditioner in environments with hazardous substances or close to equipment that
release free ames to avoid the occurrence of res, explosions or injuries.
Do not install the product in a place where thermohygrostat is needed (such as server room, machinery
room, computer room, etc.) Those places do not provide guaranteed operation condition of the product
therefore performance can be poor in these places.
Do not install the product in a ship or a vehicle (such as a campervan). Salt, vibration or other
environmental factor may cause the product malfunction, electric shock or re.
Our units should be installed in compliance with the spaces shown in the installation manual, to ensure
accessibility from both sides and allow repairs or maintenance operations to be carried out. The unit’s
components should be accessible and easy to disassemble without endangering people and objects.
For this reason, when provisions of the installation manual are not complied with, the cost required to
access and repair the units (in SAFETY CONDITIONS, as set out in prevailing regulations) with harnesses,
ladders, scaffolding or any other elevation system will NOT be considered part of the warranty and will be
charged to the end customer.
The outdoor unit shall be installed in an open space that is always ventilated.
The local gas regulations shall be observed.
To handle, purge, and dispose the refrigerant, or break into the refrigerant circuit, the worker should have
a certicate from an industry-accredited authority.
While in installation or relocation of the product, do not mix the refrigerant with other gases including air
or unspecied refrigerant. Failure to do so may cause pressure increase to result in rupture or injury.
Do not cut or burn the refrigerant container or pipings.
Use clean parts such as manifold gauge, vacuum pump, and charging hose for the refrigerant.
Installation must be carried out by qualied personnel for handling the refrigerant. Additionally, reference
the regulations and laws.
Be careful not to let foreign substances (lubricating oil, refrigerant, water, etc.) enter the pipings.
When mechanical ventilation is required, ventilation openings shall be kept clear of obstruction.
For disposal of the product, follow the local laws and regulations.
Do not work in a conned place.
The work area shall be blocked.
The refrigerant pipings shall be installed in the position where there are no substances that may result in corrosion.
The following checks shall be performed for installation:
- The charging amount depends on the room size.
- The ventilation devices and outlets are operating normally and are not obstructed.
- Markings and signs on the equipment shall be visible and legible.
Upon leakage of the refrigerant, ventilate the room. When the leaked refrigerant is exposed to ame, it
may cause generation of toxic gases.
Make sure that the work area is safe from ammable substances.
To purge air in the refrigerant, be sure to use a vacuum pump which is compatible with R-32.
Note that the refrigerant has no odour.
The units are not explosion proof so they must be installed with no risk of explosion.