Connecting the connection cord
The indoor unit is powered by the outdoor unit by means of a H07 RN-F connection cable (or a more power model), with insulation
in synthetic rubber and jacket in polychloroprene(neoprene), in accordance with the requirements of standard EN 60335-2-40.
1. Remove the screw on the electrical component box and remove the cover plate.
2. Routetheconnectioncordthroughthesideoftheindoorunitandconnectthecabletoterminals;refertothegurebelow.
3. Route the other end of the cable to the outdoor unit through the ceiling & the hole on the wall.
4. Reassemble the electrical component box cover, carefully tightening the screw.
Wiring diagram
Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible
cord. (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 / CENELEC: H07RN-F).
Screws on terminal block must not be unscrewed with the torque less than 12 kgf•cm.
Since it has the external power supply, refer to the outdoor unit installation manual for MAIN POWER.
BetweenIndoorandOutdoorConnectioncableSpecications(Commoninuse)
When installing the indoor unit in a computer room, use the double
shielded(Tape aluminum / polyester braid + copper)cable of FROHH2R type.
1 phase(∗∗052/071/090∗∗)
3 phase(∗∗100/120/140∗∗)
Indoor Power supply
Communication Cable
Power Supply Max/Min(V)
Indoor Power cable
220-240V~, 50Hz ±10%
1.5mm², 3wires
0.75~1.5mm²,2wires
Connect the rated cables only.
Connect using a driver which is able to apply the rated torque to the screws.
If the terminal is loose, re may occur caused by arc. If the terminal is
connected too rmly, the terminal may be damaged.
TighteningTorque(kgf•cm)
M3 5.0~6.0
M4 12.0~15.0
M5 20.0~25.0
CAUTION
•Alwaysremembertoconnecttherefrigerantpipesbeforeperformingtheelectricconnections.
Whendisconnectingthesystem,alwaysdisconnecttheelectriccablesbeforedisconnectingthe
refrigerantpipes.
•Alwaysremembertoconnecttheairconditionertothegroundingsystembeforeperformingthe
electricconnections.
1(L) 2(N)
NL
F1 F2
Indoor Unit
Main power cable
Cable clamp
Indoor Power
F1
F2
Communication cable
Cable tie
L(L1)
N(L2)
N
F1 F2
L3(T)
1(L) 2(N)
L2(S)
L1(R)
Cable clamp
Communication cable
Cable tie
Indoor Power
3 Phase 4 Wires
power cable(AC 380V)
Indoor Unit
L(L1)
N(L2)
F1
F2