Installation Procedure
Connecting the main power cable
When using ELB for 1 phase
ELB
MCCB
1(L) 2(N) L N F1 F2
Power Supply
The appearance of the unit may be different from the picture
depending on the model.
Cable clamp
Outdoor to indoor power cable
Cable clamp
Indoor Unit
Main power cable
Electrical
component box
Communication
cable
CAUTION
• You should connect the power cable into the power cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 2% of supply rating.
If the power is unbalanced greatly, it may shorten the life of the condenser. If the unbalanced power is exceeded over
4% of supply rating, the indoor unit is protected, stopped and the error mode indicates.
• To protect the product from water and possible shock, you should keep the power cables and the communication cable of
the indoor and outdoor units within ducts. (with appropriate IP rating and material selection for your application)
• Ensure that main supply connection is made through a switch that disconnects all poles, with contact gap of a least 3 mm.
• Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage category.
• Keep distances of 50 mm or more between power cable and communication cable.If the distance of 50mm or more cannot
be kept, a double shielded cable (FROHH2R or LiYCY type) must be used, connected to earth on a single side.
Main power terminal block specifications
[Unit : mm]
AC power:
M4 screw
1(L)
L F1
13.8 10.3
11.4
10.1
Communication: M4
screw
2(N) N F2