Installation Procedure
Step 3 Connecting the power cables,
communication cable, and controllers
You must connect the following three electrical cables to the
outdoor unit:
• The main power cable between the auxiliary circuit
breaker and the outdoor unit.
• The outdoor-to-indoor power cable between the outdoor
unit and the indoor unit.
• The communication cable between the outdoor unit and
the indoor unit.
CAUTION
• During installation, make first the refrigerant connections
and then the electrical connections. If the unit is
uninstalled, first disconnect the electrical cables and then
the refrigerant connections.
• Connect the air conditioner to the earthing system before
making the electrical connections.
NOTE
• Especially, if your outdoor unit is the one designed for
Russian and European markets, consult the supply
authority, if necessary, to estimate and reduce the supply
system impedance before installation.
Air conditioning system examples
When using earth leakage circuit breaker (ELCB) for a single
phase
Communication cable
Indoor Unit
Main power
cable
MCCB
1
Outdoor-to-indoor power cable
Outdoor Unit
Earthing
ELB
ELCB
1
OR
※Theappearanceoftheunitmaybedifferentfromthe
picture depending on the model.
CAUTION
• Make sure to install an ELCB (RCD or RCCB) or ELB and
MCB combination, according local regulations.
• If the outdoor unit is installed in a location vulnerable to
an electric leak or submergence, make sure to install an
ELCB.
• For the product that uses the R-32 refrigerant, be
cautious not to generate any sparks near the product.