34
Extra Procedures
English
Extra procedures
Using the stop valve
Opening the stop valve
1 Open the cap and turn the stop valve anticlockwise by
using a hexagonal wrench.
2 Turn it until the axis is stopped.
Tightening torque for charging port cap
(Refer to the table)
R-22: Thread of the screw - 7/16-20UNF
R-410A: Thread of the screw - 1/2-20UNF
Spindle
Charging Core
Tightening torque for body cap
(Refer to the table)
3 Tighten the cap securely.
Outer Diameter (mm)
Tightening torque
9ͱʒцʀɇΧ࣍Ęଗ࣎
Charging port cap
࣍Ęଗ࣎
Ø 6.35 20 to 25
10 to 12
Ø 9.52 20 to 25
Ø 12.70 25 to 30
Ø 15.88 30 to 35
Over Ø 19.05 35 to 40
࣍ߢĘଗߢߡ˝˙ଗʀ࣎
NOTE
Do not apply excessive force to the stop valve and
always use special instruments. Otherwise, the
stopping box can be damaged and the back sheet can
leaks.
If the watertight sheet leaks, turn the axis back by
half, tighten the stopping box, then check the leakage
again. If there is no leakage any more, tighten the axis
entirely.
Closing the stop valve
1 Remove the cap.
2 Turn the stop valve clockwise by using a hexagonal
wrench.
3 Tighten the axis until the valve reached the sealing
point.
4 Tighten the cap securely.
CAUTION
When you use the service port, always use a charging
hose, too.
Check the leakage of refrigerant gas after tightening the
cap.
Must use a spanner and wrench when you open/tighten
the stop valve.