02 INSTALLATION
15
English
Power Cable Specications
f The power cable is not supplied with air conditioner.
- Select the power supply cable in accordance with relevant local and national regulations.
- Wire size must comply with the applicable local and national code.
- Specications for local wiring power cord and branch wiring are in compliance with local cord.
Single Phase
Model Outdoor Units Input Current (Amperes) Power Supply
Outdoor Unit
Indoor Unit
Rated Voltage Range Outdoor Unit
Indoor
Unit
Total MCA (A) MFA (A)
Hz Volts Min. Max. Cooling Heating
AC012MXQFEC
AC012MNMFEC
50 220-240 198 264 9.0 - 2.5 11.5 11.5 12.7
AC018MXQFEC
AC018MNMFEC
50 220-240 198 264 18.0 - 2.5 20.5 20.5 22.6
AC024MXQFEC
AC024MNMFEC
50 220-240 198 264 18.0 - 2.5 20.5 20.5 22.6
AC030MXQFEC
AC030MNMFEC
50 220-240 198 264 24.0 - 2.5 26.5 26.5 30.0
AC036MXQFEC
AC036MNMFEC
50 220-240 198 264 24.0 - 2.5 26.5 26.5 30.0
AC042MXQFEC
AC042MNMFEC
50 220-240 198 264 32.0 - 2.5 34.5 34.5 40.0
3 Phase
Model Outdoor Units Input Current (Amperes) Power Supply
Outdoor Unit
Indoor Unit
Rated Voltage Range Outdoor Unit
Indoor
Unit
Total MCA (A) MFA (A)
Hz Volts Min. Max. Cooling Heating
AC048MXQFGC AC048MNMFEC
50 380-415 342 457 16.1 - 2.5 18.6 18.6 18.6
AC060MXQFGC AC060MNMFEC
50 380-415 342 457 16.1 - 2.5 18.6 18.6 18.6
NOTE
1. Voltage range
- Units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above
listed range limits
2. Maximum allowable voltage variation between phases is 2%.
3. Wire size & type must comply with the applicable local and national code.
- Wire size : Based on the value of MCA.
- Wire type : Supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene
sheathed exible cord (Code designation IEC:60245 IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC66
/ CENELEC H07RN-F)
4. MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
5. MCA represents maximum input current.
MFA represents capacity which may accept MCA
Abbreviations
- MCA : Min. Circuit Amps. (A)
- MFA : Max. Fuse Amps. (A)