Pump down Procedure
After installing the product, be sure to perform leak tests on the piping connections. After pumping down
refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the
connected pipes.
- Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an unconnected
or incorrectly connected pipe. Failure to do so may cause air to ow into the compressor and too a high
pressure to develop inside the refrigerant circuit, leading to an explosion or product malfunction.
WARNING
Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit.
This operation must be carried out before disconnecting the refrigerant pipe in order to avoid refrigerant loss to the
atmosphere.
1. Turn the system on in cooling with fan operating at high velocity and
then let the compressor run for more than 5 minutes. (Compressor will
immediately start, provided 3 minutes have elapsed since the last stop.)
2. Release the valve caps on High and Low pressure side.
3. Use L-wrench to close the valve on the high pressure side.
4. After approximately 2 minute, close the valve on the low pressure side.
5. Stop operation of the air conditioner by pressing the (Power) button on the
indoor unit or remote control.
6. Disconnect the pipes.
B(Liquid)
A(Gas)