Installation Procedure
Step 3 Connecting the power cables,
communication cable, and controllers
Youmustconnectthefollowingthreeelectrical
cablestotheoutdoorunit:
• Themainpowercablebetweentheauxiliarycircuit
breakerandtheoutdoorunit.
• Theoutdoor-to-indoorpowercablebetweenthe
outdoorunitandtheindoorunit.
• Thecommunicationcablebetweentheoutdoor
unitandtheindoorunit.
CAUTION
• Duringinstallation,makefirsttherefrigerant
connectionsandthentheelectricalconnections.
Iftheunitisuninstalled,firstdisconnectthe
electricalcablesandthentherefrigerant
connections.
• Connecttheairconditionertotheearthingsystem
beforemakingtheelectricalconnections.
NOTE
• Especially,ifyouroutdoorunitistheonedesigned
forRussianandEuropeanmarkets,consultthe
supplyauthority,ifnecessary,toestimateand
reducethesupplysystemimpedancebefore
installation.
Air conditioning system examples
Whenusingearthleakagecircuitbreaker(ELCB)fora
singlephase
MCCB
1
ELB
Main power
cable
Communication cable
Outdoor-to-indoor power cable
Outdoor Unit
OR
Indoor Unit
ELCB
1
Earthing
CAUTION
• Iftheoutdoorunitisinstalledinalocationvulnerabletoan
electricleakorsubmergence,makesuretoinstallanELCB.
Connecting the main power cable
When using ELCB for AC012TXQLEC (1-phase)
ELB
Power Supply
Electrical
component box
MCCB
Indoor Unit
1(L) 2(N) L N F1 F2
Cable tie
Main power
cable
Cable clamp
Outdoor to indoor
power cable
Communication
cable
The appearance of the unit may be different from the picture
depending on the model.