INSTALLATION
24
HOT WATER DELIVERY
Warning: This water heater can deliver water at temperatures which can cause scalding.
876 series – 50°C Limited Outlet
An 876 series water heater delivers water not exceeding 50°C in accordance with AS 3498. The risk of scald
injury will be reduced.
There is no need to fit a temperature limiting device to satisfy the requirements of the Plumbing Code of
Australia, if an 876 series water heater is installed and serving an application where 50°C is the maximum
permissible hot water temperature at the outlet of a fixture or appliance used primarily for personal hygiene,
such as in a bathroom or ensuite.
874 series – Hot Water Outlet
Depending upon its preset outlet temperature setting, an 874 series water heater can deliver hot water at a
temperature up to 75°C when no temperature controller is installed and 60°C when a temperature controller is
installed. These temperatures are sufficiently hot to cause severe scalding. A model used as a booster to a
solar water heater can deliver hot water exceeding these temperatures. Water at these temperatures may be
plumbed to fixtures where water hotter than 50°C is allowed, such as the kitchen and laundry.
The installing plumber may have a legal obligation to ensure the installation of this water heater meets the
water temperature delivery requirements of the Plumbing Code of Australia so that heated water delivered to
fixtures and appliances used primarily for personal hygiene is at a temperature which is unlikely to scald.
It is necessary and we recommend that a temperature limiting device be fitted between an 874 series water
heater and the fixtures and appliances used primarily for personal hygiene such as in a bathroom, ensuite,
public amenities or other ablution areas, to reduce the risk of scalding. The temperature limiting device must
be of a type suitable for use with a continuous flow gas water heater. Refer to the manufacturer’s specifications
of the temperature limiting device.
Where a temperature limiting device is installed adjacent to the water heater, the cold water line to the
temperature limiting device can be branched off the cold water line either before or after the isolation valve
and pressure limiting valve to the water heater.
If a pressure limiting valve is installed on the cold water line to the water heater and the cold water line to a
temperature limiting device branches off before this valve or from another cold water line in the premises, then
a pressure limiting valve of an equal pressure setting may be required prior to the temperature limiting device.
Two Temperature Zones Using a Temperature Limiting Device