20
INSTALLATION
THIS WATER HEATER IS FOR OUTDOOR INSTALLATION ONLY.
THIS WATER HEATER IS NOT SUITABLE FOR POOL HEATING.
Check the water heater is suitable for the gas type available.
(refer to the rating label on the water heater)
INSTALLATION STANDARDS
The water heater must be installed:
by a qualified person, and
in accordance with the installation instructions, and
in compliance with the Plumbing Code of Australia (PCA), Standards AS/NZS 3500.4 and
AS/NZS 5601.1, and all local codes and regulatory authority requirements,
The Gas installations Standard AS/NZS 5601.1 places limitations on the location of a gas water
heater within a covered area. Refer to “Installation within a Covered Area” on page 22.
874 series
Warning: This water heater may deliver water at high temperature. Refer to the Plumbing Code of
Australia, local requirements and these installation instructions to determine if additional delivery temperature
control is required. Refer to “Hot Water Delivery” on page 24.
876 series
This water heater delivers water not exceeding 50°C in accordance with AS 3498.
Warning: This water heater must only be installed in accordance with the acceptable plumbing
configurations specified in these installation instructions. Failure to do so may result in conditions where
delivery temperature control is inadequate. Refer to “Water Temperature Diagrams on page 29.
All packaging materials must be removed from the water heater prior to its installation.
WATER HEATER APPLICATION
This water heater is designed for use in a single family domestic dwelling for the purpose of heating potable
water. Its use in an application other than this may shorten its life.
If this water heater is to be used where an uninterrupted hot water supply is necessary for the application or
business, then there should be back-up redundancy within the hot water system design. This should ensure
the continuity of hot water supply in the event that this water heater was to become inoperable for any reason.
We recommend you provide advice to the system owner about their needs and building back-up redundancy
into the hot water supply system.
The 874 series of water heater may be installed as an in-series gas booster to a solar water heater. For
information relating to the function and operation of the solar water heater, refer to the Owner’s Guide and
Installation Instructions supplied with the solar water heater.
Note: The 876 series of water heater is marked “THIS APPLIANCE DELIVERS WATER NOT EXCEEDING
50°C IN ACCORDANCE WITH AS 3498” on the front panel.
The 876 series models must not be installed as an in-series gas booster to a solar water heater, as water
temperature greater than 50°C can be delivered from the water heater contravening its compliance to
AS 3498.
Note: Australian Standard AS 3498 requires that a water heater provides the means to inhibit the growth of
Legionella bacteria in potable water. When the 874 series water heater is used as an in-series booster for a
solar water heater it can satisfy this AS 3498 requirement provided it is energised, the booster preset outlet
temperature setting is 70°C or higher, and that a remote temperature controller is not used.