Proel AE604 handleiding

48 pagina's
PDF beschikbaar

Handleiding

Je bekijkt pagina 22 van 48
22
USRMAN_AE604EN_REV003
IDLE Charger at rest
Charger temp:
PROBE FAILURE Charger circuit temperature probe faulty
OVERTEMP Overheating of the charger circuit; temperature out of range
OK Charger circuit temperature correctly in range
If one of the following indications appears, consult the list of faults:
PSU COMMUNICATION LOSS Communication fault with PSU
FLASH FAILURE PSU Microprocessor fault
WATCHDOG RESET PSU Microprocessor fault
The Thermal management system menù allows You to view the temperatures detected by the system:
Thermal status:
DISABLED Disabled (Disablement)
FAULT Faulty
OK Properly functioning
PSU temp: (Main Power Supply temperature)
PROBE FAILURE Main power supply temperature probe faulty
OVERTEMP Overheating of Main power supply
OK Main power supply temperature correctly in range
Batt temp:
PROBE SHORT Battery pack temperature probe in short circuit
PROBE OPEN Battery pack temperature probe open or removed
OVERTEMP Overheating of the battery pack; temperature out of range
UNDERTEMP Battery pack temperature below threshold.
OK Battery pack temperature correctly in range.
Charger temp:
PROBE FAILURE Charger circuit temperature probe faulty
OVERTEMP Overheating of the charger circuit; temperature out of range
OK Charger circuit temperature correctly in range
For completeness, the temperature measured at the various sections is displayed; if there is a probe
failure, the temperature display is suppressed.
If one of the following indications appears, consult the list of faults:
PSU COMMUNICATION LOSS Communication fault with PSU
FLASH FAILURE PSU Microprocessor fault
WATCHDOG RESET PSU Microprocessor fault
From one of the detail screens, pressing OK you can access the POP-UP in which you can put or remove
the disablement condition of the section.
When the "Power supply unit" section is in "disablement" all the safety functions related to the power
supply are disabled. Any "FAULTS" errors are also removed. The "disablement" function allows you to
operate on the batteries without interrupting system operation and without generating "FAULTS" errors.

Bekijk gratis de handleiding van Proel AE604, stel vragen en lees de antwoorden op veelvoorkomende problemen, of gebruik onze assistent om sneller informatie in de handleiding te vinden of uitleg te krijgen over specifieke functies.